Chapter 1 Safety Instructions
1 - 10
1.3 Precautions Concerning Compliance with UL and cUL Standards
(Standard to comply with : UL508C,CSA C22.2 No.14-05)
a) Maximum surrounding air temperature rating of 50ºC.
b) Solid State motor overload protection reacts with max. 150 % of FLA.
c) Suitable for use on a circuit capable of delivering not more than 100,000 rms Symmetrical Amperes,
240 Volts Maximum. For models 200V class.
Suitable for use on a circuit capable of delivering not more than 100,000 rms Symmetrical Amperes,
480 Volts Maximum.For models 400V class.
d) Drive has no provision for motor over temperature protection.
e) When protected by J, CC, G or T Class Fuses. or When protected by a circuit breaker having an
interrupting rating not less than 100,000 rms symmetrical amperes, 240 Volts maximum. For models
200V class.
When Protected by J, CC, G or T Class Fuses. For models 400V class.
f) Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code and any additional local
codes.
g) Install device in pollution degree 2 environment
h) Branch circuit short circuit protection can use fuse or circuit breaker only. For models 200V class..
Branch circuit short circuit protection can use fuse only. For models 400V class..
i)
Use 60/75ºC CU wire only.
j)
Tightening torque and wire range as shown in the table below.
Model No.
Required Torque (N.m)
Wire Range(AWG)
NES1-002S,004S
0.8~1.0
16~14
NES1-007S
1.8
14~12
NES1-015S
1.8
12~10
NES1-022S
1.8
10
NES1-002L,004L,007L
0.8~1.0
16~14
NES1-015L
1.8
14
NES1-022L
1.8
12
NES1-004H,007H,015H
1.8
16
NES1-022H,040H
1.8
14
j) Distribution fuse and circuit breaker size marking is included in the manual to indicate that the unit
shall be connected with a Listed Cartridge Nonrenewable fuse or Inverse time circuit breaker, rated
600 VAC with the current ratings as shown in the table below:
* In case of using Circuit Breaker, an additional 5 A external protector is needed.
Model No.
Fuse
Circuit Breaker
Type Maximum Rating
Type
Maximum Rating
NES1-002S,004S
Class J, CC, G or T
10 A
Inverse
Time
15 A
NES1-007S 20
A
NES1-015S,022S
30 A
30 A
NES1-002L*,004L*
Class J, CC, G or T
10 A
Inverse
Time
15 A
NES1-004L*
NES1-007L*,015L 15
A
NES1-022L
20 A
20 A
NES1-004H,007H,
015H,022H,040H
Class J, CC, G or T
15A
-
-
PD
R
S
T
U
V
W
P
Inverter
Power
supply
Motor
DC link choke
Circuit breaker or
Fuse
Wiring diagram of inverter
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...