Chapter 6 Operation
6 - 11
6.6 Motor Operation
Both “Run command” and “frequency command” is necessary to run the motor. Motor does not run if one
of each is missing. For example, motor will not run when a run command is given, but a frequency
command is 0Hz. Additionally, the motor will not run if a FRS (free run stop) signal (and the like) is being
given.
NE-S1 series inverter has following way to set the run command and frequency command. (This is an
example of sink logic and uses internal control power supply.)
(A) Driving with the standard panel
RUN/STOP/RESET key on the standard operation panel is effective regardless of the setting of the
driving order method(A002). Thus, following driving method (1) to (3) is possible without an option if it is
factory default setting.
(1)Method to perform driving in RUN/STOP/RESET key and perform frequency setting in Multispeed
select
This is the operation method using Run command is given by "RUN/STOP/RESET key" & Frequency
setting is given by Fixed value such as 20/40/60Hz, Accel&Decel time is 10 seconds. If you don't need
to change such as Accel&Decel time, optional Operator is not required.) To set the Freq. setting, use
the Multi-speed frequency setting (1=60Hz),(2=40Hz),(3=20Hz).
■
Setup
Function Name
Code
Data
Note
Input [3] function
C003
02(CF1)
Default
Input [4] function
C004
03(CF2)
The initial value of Acceleration/ Deceleration time is 10sec.
Please change the following parameters as needed.
Function Name
Code
Setting Range
Note
Acceleration time
F002
0.00 to 3600sec.
Default
:
10 sec.
Deceleration time
F003
0.00 to 3600sec.
Default
:
10 sec.
* One of the following is required when changing parameters on NE-S1 series inverters.
a) Dedicated operator (NES1-OP)
b) Digital operator c) 5-line LCD operator
d) Modbus e) PC programming tool (ProDriveNext)
■
Control circuit terminals wiring (Sink logic)
■
Example of use
(
default
)
Restricted
Distribution
Other
(
Standard
)
Restricted
Distribution
China / Europe
Code
Intelligent
input terminal
[3]
Intelligent
input terminal
[4]
60Hz order
50Hz order
A021(multi- speed freq. 1)
OFF
ON
40Hz order
35Hz order
A022(multi- speed freq. 2)
ON
OFF
20Hz order
20Hz order
A023(multi- speed freq. 3)
ON
ON
P24
PLC
L
3
CF1
CF2
4
…
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...