Chapter 13 Option
13 - 28
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name
Description
Initial data
standard
200/400
Initial data
CHN
200/400
Initial data
EU
200/400
Units
A038
(Jog
frequency)
Jog frequency
Defines limited
speed for jog, range
is from start
frequency to 9.99
Hz
6.00
←
←
Hz
A039
(Jog stop
mode)
Jog stop mode
Define how end of
jog stops the motor;
six options:
00
Free-run stop
(invalid during
run)
01
Controlled
deceleration
(invalid during
run)
02
DC braking to
stop(invalid
during run)
03
Free-run stop
(valid during
run)
04
Controlled
deceleration
(valid during
run)
05
DC braking to
stop(valid
during run)
04
←
←
A041
(TRQ
boost sel)
Torque boost select
Two options:
00
Manual torque
boost
01
Automatic
torque boost
00
←
←
A241
(TRQ
boost sel-M2)
Torque boost select, 2
nd
motor
00
←
←
A042
(TRQ
boost V%)
Manual torque boost
value
Can boost starting
torque between 0
and 20% above
normal V/f curve,
range is 0.0 to
20.0%
1.0 3.0 1.0
%
A242
(TRQ
boost V%-M2)
Manual torque boost
value, 2
nd
motor
1.0 3.0 1.0
%
A043
(TRQ
boost FQ%)
Manual torque boost
frequency
Sets the frequency
of the V/f breakpoint
A in graph (top of
previous page) for
torque boost,
range is 0.0 to
50.0%
5.0
←
←
%
A243
(TRQ boost
FQ%-M2)
Manual torque boost
frequency,
2
nd
motor
5.0
←
←
%
A044
(V/F select)
V/f characteristic curve
Three available V/f
curves;
00
Constant
torque
01
Reduced
torque (1.7)
02
Free V/F
00
←
←
A244
(V/F
select-M2)
V/f characteristic curve,
2
nd
motor
00
←
←
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...