Chapter 7 Explanation of Functions
7 - 13
7.3.3 Input terminal response time
- The input terminal response time function allows you to specify a sampling time for each of intelligent input terminals
1 to 5. You can use this function effectively to remove noise (e.g., chattering).
- If chattering hinders constant input from an input terminal, increase the response time setting for the input terminal.
Note that an increase in response time deteriorates the response. The response time can be set in a range of about 2
to 400 ms (corresponding to settings of 0 to 200).
Item
Function code
Range of data
Description
Response time of intelligent
input terminals 1 to 5
C160-C164
0. to 200.
Variable in step of 1
Note: When the power supply is OFF-> ON or reset , this function is invalid.
7.3.4 Intelligent output terminal setting
You can assign the functions described below to the intelligent output terminals [11] (C021) and the alarm
relay terminal (C026).
The intelligent output terminals [11] is used for open-collector output, and the alarm relay terminal is used
for relay output.
You can select the a-contact or b-contact output for individual output terminals by using functions "C031"
and "C036".
Data Description
Reference
item Page
00
RUN: Running signal
Running signal (RUN)
7-68
01
FA1: Constant-speed reached
Frequency-arrival signals
7-68
02
FA2: Set frequency overreached
03
OL: Overload notice advance signal
Overload restriction/overload notice advance signal
7-63
04
OD: Output deviation for PID control
PID function
7-37
05
AL: Alarm signal
Protective functions
-
06
FA3: Set frequency reached
Frequency-arrival signals
7-68
09 UV:
Undervoltage
undervoltage
7-53
11
RNT: Operation time over
Operation time over signal
7-70
12
ONT: Plug-in time over
Plug-in time over signal
7-70
13
THM: Thermal alarm signal
Electronic thermal protection
7-62
21
ZS: 0 Hz detection signal
0 Hz detection signal
7-70
27
Dc: Analog O/OI disconnection detection
Window comparators function
7-75
31
FBV: PID feedback comparison
PID function
7-34
32
NDc: Communication line disconnection
RS485
7-72
33
LOG1: Logical operation result 1
Logical operation function
7-71
41
FR: Starting contact signal
Starting contact signal
7-72
42
OHF: Heat sink overheat warning
Heat sink overheat warning
7-72
43
LOC: Low-current indication signal
Low-current indication signal
7-73
50
IRDY: Inverter ready
Inverter ready signal
7-73
51
FWR: Forward rotation
Forward rotation signal
7-73
52
RVR: Reverse rotation
Reverse rotation signal
7-74
53
MJA: Major failure
Major failure signal
7-74
54
WC:Window Comparator for Analog Voltage
Input
Window comparators function
7-75
58
FREF:Frequency Command Source
Frequency Command Source signal
7-76
59
REF:Run Command Source
Run Command Source signal
7-76
60
SETM:2nd Motor Selection
2nd Motor Selection signal
7-76
no NO:
Allocation
none
-
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...