Chapter 13 Option
13 - 36
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name
Description
Initial data
standard
200/400
Initial data
CHN
200/400
Initial data
EU
200/400
Unit
s
b001
(Restart
mode UV)
Restart mode on
power failure /
under-voltage trip
Select inverter restart
method,
Four option codes:
00
Alarm output after
trip, no automatic restart
01
Restart at 0Hz
02
Resume operation
after frequency matching
03
Resume previous
freq. after freq. matching,
then decelerate to stop
and display trip info
00
←
←
b002
(Allowable
UV time)
Allowable
under-voltage power
failure time
The amount of time a
power input
under-voltage can occur
without tripping the power
failure alarm. Range is
0.3 to 25.0 sec. If
under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.
1.0
←
←
s
b003
(Retry wait
time UV)
Retry wait time
before motor restart
Time delay after
under-voltage condition
goes away, before the
inverter runs motor again.
Range is 0.3 to 100.0
seconds.
1.0
←
←
s
b004
(UV trip on
stop)
Instantaneous power
failure /
under-voltage trip
alarm enable
Three option codes:
00
Disable
01
Enable
02
Disable during stop
and decelerates to a stop
00
←
←
b005
(No. of restart
UV)
Number of restarts
on power failure /
under-voltage trip
events
Two option codes:
00
Restart 16 times
01
Always restart
00
←
←
b007
(Restart
min.FQ)
Restart frequency
threshold
Restart the motor from
0Hz if the frequency
becomes less than this
set value during the motor
is coasting, range is 0.00
to 400.00Hz
0.50
←
←
Hz
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...