Chapter 13 Option
13 - 40
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name
Description
Initial data
standard
200/400
Initial data
CHN
200/400
Initial data
EU
200/400
Unit
s
b036
(Reduced V
start)
Reduced voltage
start selection
Set range, 0 (disabling
the function), 1 (approx.
4ms) to 250 (approx. 1s)
3
←
←
b037
(Display
restriction)
Function code
display restriction
Five option codes:
00
Full display
01
Function-specific
display
03
Data comparison
display
04
Basic display
05
Monitor display only
00
←
←
b038
(Initial
display)
Initial display
selection
000
Func. code that
SET key pressed last
displayed.(*)
001~060
d001~d060
displayed
201
F001displayed
202
B display of LCD
operator (In case of
Digital operator, same
000 setting)
001
←
←
b050
(Ctrld
decel.select)
Controlled
deceleration on
power loss
Four option codes:
00
Disabled
01
Decelerates to a stop
02
Decelerates to a stop
with DC bus voltage
controlled
03
Decelerates to a stop
with DC bus voltage
controlled, then restart
00
←
←
b051
(DC Volt
ctrld.decel)
DC bus voltage
trigger level of ctrl.
decel.
Setting of DC bus voltage
to start controlled decel.
operation. Range is 0.0 to
400.0/800.0
220.0/
440.0
←
←
V
b052
(OV lvl
ctrld.decel)
Over-voltage
threshold of ctrl.
decel.
Setting the OV-LAD stop
level of controlled decel.
operation. Range is 0.0 to
400.0/800.0
360.0/
720.0
←
←
V
b053
(Decel time
ctrld.dec)
Deceleration time of
ctrl. decel.
Range is 0.01 to 300.00
seconds.
1.00
←
←
s
b054
(FQ drop
ctrld.decel)
Initial freq. drop of
ctrl. decel.
Setting of initial freq.
drop.
Range is 0.00 to 10.00 Hz
0.00
←
←
Hz
b060
(Windw comp
[O/OI] max)
Maximum-limit level
of window
comparator (O/OI)
Set range, {Min.-limit level
(b061) + hysteresis width
(b062)x2} to 100 %
100.
←
←
%
b061
(Windw comp
[O/OI] min)
Minimum-limit level
of window
comparator (O/OI)
Set range, 0 to {Max.-limit
level (b060) - hysteresis
width (b062)x2}maximum
of 100 %
0.
←
←
%
b062
(Windw comp
[O/OI] hys)
Hysteresis width of
window comparator
(O/OI)
Set range, 0 to {Max.-limit
level (b060) - Min.-limit
level (b061)}/2 %
(Maximum of 10%)
0.
←
←
%
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...