12. Maintenance notes
457
SMGB0079 rev.0 - 01/2013
12
12.1.3 Insufficient cooling performance when a long piping is applied
Question and answer for the field work
Example 2: Insufficient cooling performance when a long piping is applied
Phenomenon
Sufficient cooling was not available for an indoor unit that was located at the farthest position.
Cause
If the location of an outdoor unit is 20 meters lower than the location of the indoor units resetting of the DIP switch DSW3
is required.
However no setting was performed. Therefore the largest discharge pressure was not increased. This resulted in an in-
sufficient cooling performance for the indoor unit.
Outdoor unit
Indoor units
Insufficient cooling
Countermeasure
The setting of the DSW2 was changed.
Remarks
Pay special attention to the size of liquid pipe. Refer to
Piping work and refrigerant charge
chapter for details.
12.1.4 Abnormally high operation sound (in the ceiling type indoor unit).
Question and answer for the field work
Example 3: Abnormally high operation sound (in-the-ceiling type indoor unit)
Phenomenon
The operation sound at the “HIGH” speed was abnormally high.
Cause
The indoor units were installed without the ducts. Since there scarcely was any external static pressure an abnormally big
air volume was supplied. This resulted in a higher air speed through the heat exchanger.
Damper
Indoor unit
A. Filter
Countermeasure
In order to reduce the airflow rate a plate that is used as a damper at the discharge gas side was added.
Remarks
Note that the running current is increased when no external pressure is given to the indoor unit. This results in an over-
heating.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......