8. Troubleshooting
212
SMGB0079 rev.0 - 01/2013
Alarm code
08
Excessively High Discharge Gas Temperature at the Top of Compressor
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
• The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
-
The alarm appears during cooling operation when the compressor-top thermistor remains at Tdc 1 °C or above for
10 minutes, or at Tdc 2 °C or above for 5 seconds.
-
The alarm appears during heating operation when the compressor-top thermistor remains at Tdh 1 °C or above for
10 minutes, or at Tdh 2 °C or above for 5 seconds.
Outdoor capacity
Tdc1
Tdc2
Tdh1
Tdh2
RAS-(2-6)H(V)N(P/C)(E)
115
125
115
125
RAS-(8-12)HNP(E)
127
135
120
135
RAS-(8-12)HNC(E)
127
140
120
140