3. Piping work and refrigerant charge
66
SMGB0079 rev.0 - 01/2013
3.3.4 Combinations of piping size and piping length
IVX Premium series
Liquid
Ø6.35
Ø9.52
Ø12.70
Ø15.88
Gas
Ø9.52
Ø12.70
Ø15.88
Ø19.05
Ø12.70
Ø15.88
Ø19.05
Ø22.20
Ø25.40
Ø15.88
Ø19.05
Ø22.20
Ø25.40
Ø28.60
Ø22.20
Ø25.40
Ø28.60
Performance
capacity
(m)
2 HP
15
(1)
50
30
-
15
(3)
15
(3)
-
-
-
-
-
-
-
-
-
-
-
2.5 HP
-
50
30
-
20
(3)
20
(3)
-
-
-
-
-
-
-
-
-
-
-
3 HP
-
30
(1)(2)
30
(2)
-
30
(1)
50
-
-
-
-
-
-
-
-
-
-
-
4 - 5 - 6
HP
-
-
5
(2)
5
(2)
40
(1)
75
50
(4)
-
-
30
(3)
30
(3)
(4)
-
-
-
-
-
-
8 HP
-
-
-
-
-
-
50
(1)(4)(6)
50
(1)(6)
70
(5)(7)
-
50
(1)(3)(4)
50
(1)(3)
100
-
50
(1)(3)
50
(3)
-
10 - 12 HP
-
-
-
-
-
-
-
-
-
-
-
50
(1)
100
50
50
(1)(3)
50
(3)
50
(3)
(1).Reducing gas pipe size will lower cooling capacity due to larger pressure loss in gas piping and narrow operation range.
(2).Reducing liquid pipe size will narrow operation range due to indoor unit relation with expansion valve capacity.
(3).Increasing liquid pipe size will require additional refrigerant charge.
(4).When using Ø19.05 gas pipe (soft-annealed), please switch ON DSW2-4# in the Outdoor Unit PCB.
(5) In case that pipe length exceeds 70m in 8 HP, please use a
Ø
12.7 pipe as a liquid pipe.
(6).In case of exceeding the recommended number of connected Indoor Units of 8 HP (more than 5 Units), please use a
Ø
12.7 pipe as a liquid
Standard
IVX Standard series
Liquid
Ø6.35
Ø9.52
Ø12.70
Ø15.88
Gas
Ø9.52
Ø12.70
Ø15.88
Ø19.05
Ø12.70
Ø15.88
Ø19.05
Ø22.20
Ø25.40
Ø15.88
Ø19.05
Ø22.20
Ø25.40
Ø28.60
Ø22.20
Ø25.40
Ø28.60
Performance
capacity
(m)
3 HP
-
30
(1)(2)
30
(2)
-
30
(1)
50
-
-
-
-
-
-
-
-
-
-
-
4 HP
-
-
5
(2)
5
(2)
40
(1)
70
50
(4)
-
-
30
(3)
30
(3)
(4)
-
-
-
-
-
-
5 - 6 HP
-
-
5
(2)
5
(2)
40
(1)
75
50
(4)
-
-
30
(3)
30
(3)
(4)
-
-
-
-
-
-
8 HP
-
-
-
-
-
-
50
(1)(4)
50
(1)
70
(5)
-
50
(1)(3)(4)
50
(1)(3)
100
50
(1)(3)
50
(3)
10 - 12 HP
-
-
-
-
-
-
-
-
-
-
-
50
(1)
100
50
50
(1)(3)
50
(3)
50
(3)
(1).Reducing gas pipe size will lower cooling capacity due to larger pressure loss in gas piping and narrow operation range.
(2).Reducing liquid pipe size will narrow operation range due to indoor unit relation with expansion valve capacity.
(3).Increasing liquid pipe size will require additional refrigerant charge.
(4).When using Ø 19.05 gas pipe (soft-annealed), please switch ON DSW2-4# in the Outdoor Unit PCB.
(5) In case that pipe length exceeds 70m in 8 HP, please use a
Ø
12.7 pipe as a liquid pipe.
(6).In case of exceeding the recommended number of connected Indoor Units of 8 HP (more than 5 Units), please use a
Ø
12.7 pipe as a liquid
Standard
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......