8. Troubleshooting
208
SMGB0079 rev.0 - 01/2013
Alarm code
06
Excessively low voltage or excessively high voltage for the inverter
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
• The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
• The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
-
This alarm code is displayed when the voltage between terminal “P” and “N” of Inverter is insufficient and the alarm
has three occurrences in 30 minutes. If the number of occurrences is smaller than two, the retry operation is per-
formed. The alarm code “06.” Means fan controller Abnormal Operation.
RAS-(2-2.5)HVNP / RAS-3HVNC
N O T E
Relpace electrical box only when LED is OFF.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......