3. Piping work and refrigerant charge
69
SMGB0079 rev.0 - 01/2013
3
Line branch system
A
B
C
D
(mm)
Multi-kit model A
Multi-kit model B
Outdoor Unit HP
Pipe Size (D)
IVX Premium Series IVX Standard Series IVX Premium Series IVX Standard Series
Gas
Liquid
3 / 4 / 5 / 6
Ø15.88
Ø9.52
E-102SN2
E-102SN2
E-102SN2
E-102SN2
8
Ø25.40 Ø9.52
(1)
E-162SN2
E-162SN2
E-102SN2
E-102SN2
10 /12
Ø25.40 Ø12.70
E-162SN2
E-162SN2
E-102SN2
E-102SN2
(1) In case that total pipe length from the outdoor to the farthest indoor unit exceeds of 70m in 8 HP unit, please use a Ø12.7 pipe as a liquid pipe.
(mm)
Indoor Unit capacity
Pipe Size (C)
Gas
Liquid
≤ 1.5 HP
Ø12.70
Ø6.35
1.8 / 2.0 HP
Ø15.88
Ø6.35
> 2.3 HP
Ø15.88
Ø9.52