2. Unit Installation
24
SMGB0079 rev.0 - 01/2013
4
The whole of the base of the outdoor unit should be installed on a foundation. When using vibration-proof mat it should
also be positioned the same way. When installing the outdoor unit on a field-supplied frame use metal plates to adjust
the frame width for stable installation as shown in Figure.
1. Outdoor unit is unstable
2. Frame
3. Outdoor unit is stable
4. Metal plate
A. 57 mm. Base width of outdoor unit
B. 60 mm Frame width (Field-supplied)
C. 100 mm or more Metal plate
• Recommended Metal Plate Size:
-
(Field-Supplied) Material: Hot-Rolled Mild Steel.
-
Plate (SPHC) Plate Thickness: 4.5 T
120
60
(560)
70
420
70
20
14
R
4-C10
320
(460)
Installing location where the unit will be exposed to strong wind
Follow the instructions below to install on the rooftop or a location without surrounding buildings where strong wind is ex-
pected against the product.
1
Choose a location where the outlet or inlet side of the product
will not be exposed to strong wind.
2
When the outlet is exposed to strong wind: Direct strong wind
may cause lack of air flow and adversely affect to normal
function.
C A U T I O N
Excessive strong wind against the outdoor unit outlet may cause inverse rotation and damage the fan and motor.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......