3. Piping work and refrigerant charge
64
SMGB0079 rev.0 - 01/2013
IVX Standard series
(m)
Outdoor Unit
3HP
4HP
5HP
6HP
8HP
10HP
12HP
Maximum piping length
between the outdoor unit
and the farthest indoor
unit
Actual Length (L)
50
70
75
100
Equivalent Length (EL)
70
90
95
125
Total piping length
2 units (A+B+C)
60
80
85
100
115
3 units (A+B+C+D)
--
90
95
100
130
4 units
(A+B+C+D+E+F+G+)
--
90
95
100
145
Maximum piping line
after first branch
2 and 3 units (B, C, D)
10
15
4 units
(B+D, B+E, C+F, C+G)
--
10
15
Main piping length A
A > B, C, D, E, F, G
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
30 / 20
Maximum height difference Indoor / Indoor
3
Maximum height difference:
branch pipe/Indoor (2,3 and 4 indoor units system)
branch pipe/branch pipe (4 indoor units system)
3
(B-C) / (B-D) / (C-D) / (C+G)-(B+E) / (C+G)-(B+D) /
(C+F)-(B+E) / (C+F)-(B+D)
< 8
N O T E
• The liquid piping and the gas piping must be of the same piping length and run along the same route.
• Install the branch piping as much as possible near the indoor units
• Install Multikits at the same horizontal level.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......