3. Piping work and refrigerant charge
54
SMGB0079 rev.0 - 01/2013
3.1.2 Three principles on refrigerant piping work
In case of using refrigerant R410A in the refrigeration cycle, the refrigeration oil should be of a synthetic type one.
In order to avoid oxidation, pay much careful attention to basic piping work control to avoid infiltration of moisture or dust
during the refrigerant piping work.
Three principles
Cause of failure
Presumable failure
Preventive action
1. Dry
Keep good dryness
• Water infiltration due to
insufficient protection at pipe
ends
• Dewing inside of pipes
• Insufficient vacuum pumping
time
Icing inside tube at ex. valve
(Water choking)
+
Generation of hydration and oxida-
tion of oil
↓
Clogged strainer, etc., insulation
failure and compressor failure
Pipe protection
1 Pinching
2 Taping
↓
Flushing
↓
Vacuum Drying
• One gram of water turns into gas
(approx. 1000 lrs) at 1 Torn
• Therefore, it takes long time to
vacuum-pump by a small vacuum
pump
2. Clean
No dust inside of
pipes
• Infiltration of dust or other
through the pipe ends.
• Oxidation film during brazing
without blowing nitrogen.
• Insufficient flushing by nitrogen
after brazing
Clogging of expansion valve, capil-
lary tube and filter
→Oxidation of oil
→Compressor failure
↓
Insufficient cooling or heating com-
pressor failure
Pipe Protection
1 Mounting Caps
2 Taping
3 Pinching
↓
Flushing
3. No leakage
No leakage shall
exist
• Brazing failure
• Failed flaring work and insuffi-
cient torque of squeezing flare
• Insufficient torque of squeezing
flanges
Refrigerant shortage
→Performance decrease
→Oxidation of oil
→Overheating of compressor
↓
Insufficient cooling or heating com-
pressor failure
Careful Basic Brazing Work
↓
Basic Flaring Work
↓
Basic Flange Connecting Work
↓
Air Tight Test
↓
Holding of Vacuum
3.1.3 Suspension of refrigerant piping
Suspend the refrigerant piping at certain points and prevent the refrigerant piping from touching weak parts of the building
such as walls, ceiling, etc. (If touched, abnormal noises may occur due to the vibration of the piping. Pay special attention
in case of short piping length).
A. Fire-proof section treatment.
B. Indoor unit.
In order to fix the piping to wall or ceilings use suspension and clamping systems as shown in the following figure.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......