3. Piping work and refrigerant charge
58
SMGB0079 rev.0 - 01/2013
For the front and side piping
Select the correct knock-out size depending on whether it is for power wiring or transition wiring
RAS-3HVNPE / RAS-(4-6)H(V)N(P/C)E / RAS-(8-10)HN(P/C)E
RAS-12HN(P/C)
Front piping hole
Rigth side
piping hole
Front-SIde Piping Hole
Right-SIde Piping Hole
A
A
B
B
Front piping hole
Right side piping hole
To use racking or conduit tubes, check the size and remove
part following the slit.
N O T E
Place insulation (field supplied) to protect cables and pipes from being damaged by plate edges.
For the downward piping
After removing the bottom of the piping cover, perform piping and wiring works.
RAS-3HVNPE / RAS-(4-6)H(V)N(P/C)E / RAS-(8-10)HN(P/C)E
RAS-12HN(P/C)
Gas piping
Knock-out hole
Bottom base
Cables
Liquid piping
Liquid
Piping
Gas
Piping
Wiring
Bottom Base
Bottom-Side Piping Hole
Piping Cover
Fixing Screw
(1 Portion)
Knock-out hole
Bottom base
Wiring
Liquid
piping
Gas
piping
Piping cover
Fixing screw
(1 portion)
N O T E
Cables shall not contact directly to the pipes.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......