8. Troubleshooting
214
SMGB0079 rev.0 - 01/2013
Alarm code
12
Abnormal operation of the thermistor for the indoor discharge air temperature (air outlet thermistor)
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
• The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
-
This alarm code is displayed when the thermistor is short-circuited (less than 0.24 kΩ) or cut (greater than 840 kΩ)
during the cooling process or the heating process. The system is automatically restarted when the fault is removed.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Faulty air outlet thermistor
Fault
Check the resistance
Replace the thermistor if faulty
Incorrect connection
Check the connection
Repair the wiring and connections
Faulty PCB
Replace PCB and
check the operation