2. Unit Installation
14
SMGB0079 rev.0 - 01/2013
2.1 Safety summary
D A N G E R
•
Install the outdoor unit with sufficient clearance around it for operation and maintenance as shown in the next
pages.
•
Install the outdoor unit where good ventilation is available.
•
Do not install the outdoor unit where exists a high level of oil mist, salty air or sulphurous atmosphere.
•
Install the outdoor unit as far as practical (being at least 3 meters) from electromagnetic wave radiator such
as medical equipment.
•
Keep clearance between units of more than 50 mm and avoid obstacles that could hamper air intake when
installing more than one unit together.
•
Install the outdoor unit in the shade or not exposed to direct sunshine or direct radiation from high tempera-
ture heat source.
•
Do not install the outdoor unit in a place where a seasonal wind directly blows into the outdoor fan.
•
For cleaning use non-inflammable and nontoxic cleaning liquid. Use of inflammable agent may cause explo-
sion or fire.
•
Work with sufficient ventilation. Working in an enclosed space could cause oxygen deficiency. Toxic gas may
be produced when cleaning agent is heated to high temperature by e.g. being exposed to fire.
•
Cleaning liquid shall be collected after cleaning.
•
Pay attention to do not clamp cables when attaching the service cover to avoid electric shock or fire.
C A U T I O N
•
Check the foundation to be flat leveled and strongly enough.
•
Install the unit in a restricted area not accessible by the general public.
•
Aluminium fins have very sharp edges. Pay attention to the fins in order to avoid injury.
•
Do not install the indoor units in a flammable environment to avoid a fire or an explosion.
•
Check to ensure that the ceiling slab is strong enough. If not strong enough the indoor unit may fall down on
you.
•
Do not install the indoor units outdoor unit remote control switch and cable within approximately 3 meters
from strong electromagnetic wave radiators such as medical equipment.
•
Do not install the indoor units in a machinery shop or kitchen where vapour from oil or mist flows to the in-
door units. The oil will deposit on the heat exchanger thereby reducing the indoor unit performance and may
deform. In the worst case the oil damages the plastic parts of the indoor unit.
•
To avoid any corrosive action to the heat exchangers do not install the indoor units in an acid or alkaline en-
vironment.
•
When lifting or moving the indoor unit use appropriate slings to avoid damage and be careful not to damage
the insulation material on units surface.
•
This appliance must be used only by adult and capable people having received the technical information or
instructions to handle properly and safely this appliance.
•
Turn OFF all power switches before maintenance is performed.
•
Do not start the cleaning procedures before 5 minutes of the stop of the unit.
D A N G E R
•
Avoid obstacles which may hamper the air intake or the air discharge flow.
•
Children must be supervised to ensure that they do not play with the electrical appliances.
•
Before obtaining access to terminals all supply circuits must be disconnected.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......