4. Electrical wiring
89
SMGB0079 rev.0 - 01/2013
4
MODEL
Z max (Ω)
MODEL
Z max (Ω)
RAS-2HVNP
-
RAS-2.5HVNP
-
RAS-3HVNPE
0.39
RAS-3HVNC
-
RAS-4HVNPE
0.27
RAS-4HVNCE
0.27
RAS-5HVNPE
0.27
RAS-5HVNCE
0.27
RAS-6HVNPE
0.27
RAS-6HVNCE
0.27
RAS-4HNPE
-
RAS-4HNCE
-
RAS-5HNPE
-
RAS-5HNCE
-
RAS-6HNPE
-
RAS-6HNCE
-
RAS-8HNPE
-
RAS-8HNCE
-
RAS-10HNPE
-
RAS-10HNCE
-
RAS-12HNP
-
RAS-12HNC
-
3
Harmonics situation of each model regarding IEC 61000-3-2 and IEC 61000-3-12 is as follows:
MODELS SITUATION REGARDING
IEC 61000-3-2 and IEC 61000-3-12
MODEL
Equipment complying with IEC 61000-3-2
(*) professional use
RAS-2HVNP
RAS-2.5HVNP
RAS-3HVNC
RAS-4HNPE (*)
RAS-5HNPE (*)
RAS-6HNPE (*)
RAS-4HNCE (*)
RAS-5HNCE (*)
RAS-6HNCE (*)
Equipment complying with IEC 61000-3-12
RAS-3HVNPE
RAS-4HVNPE
RAS-5HVNPE
RAS-6HVNPE
RAS-4HVNCE
RAS-5HVNCE
RAS-6HVNCE
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or
equal to xx (see Ssc column) at the interface point between the user’s supply and the public system. It is
the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a short-circuit power
Ssc greater than or equal to xx (see Ssc column)
MODEL
Ssc “xx” (KVA)
Installation restrictions may be applied by supply authorities in relation to harmonics
MODEL
RAS-8HNPE
RAS-8HNCE
RAS-10HNPE
RAS-10HNCE
RAS-12HNP
RAS-12HNC
D A N G E R
• Never connect the earth cable to the refrigerant pipes. The gas in the pipes could cause a fire.
• Do not connect the earth cable to the lighting arrest system. The electrical potential of earth would increase
abnormally.
5
Check to ensure that the power supply voltage is /-10% of the rated voltage.
6
Check to ensure that power supply has an impedance low enough to warranty not reduce the starting voltage more
than 85% of the rated voltage.
7
Check to ensure that the ground wire is connected.
8
Connect a fuse of specified capacity.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......