6. Optional functions
149
SMGB0079 rev.0 - 01/2013
6
RAS-3HVNPE / RAS-(4-12)H(V)N(P/C)(E)
Input signals
Ind.
Input signal
Application
Port
0
No setting application
No setting
—
1
Fixing the heating mode
This signal allows to pre-fix the operation mode, in this case the heating
mode, independently of what the indoor unit requests. If the indoor units
request the oposite mode than the outdoor unit, the compressor will not start.
This is very useful to set up a unique operation mode.
CN1 and CN2
2
Fixing the cooling mode
This signal allows to pre-fix the operation mode, in this case the cooling
mode, independently of what the indoor unit requests. If the indoor units
request the oposite mode than the outdoor unit, the compressor will not
start. This is very useful for computer rooms where the cooling mode is fixed
throughout the year.
CN1 and CN2
3
Demand thermo OFF
This signal allows to stop the compressor if it reaches a certain power as well
as to put the indoor unit in Thermo-OFF. This is very useful for installations
with high power consumption. This signal is only activated if function F1 has
value 1.
CN1 and CN2
4
No setting application
No setting
—
5
Forced stoppage
This signal allows to control the stoppage of the compressor and the fans of
the indoor as well as outdoor units. This is very useful when used with the
alarm signals of the fire prevention systems. This signal is only activated if
function F1 has value 1.
CN1 and CN2
6
Current control demand 60%
This signal allows to regulate current consumption and establish an average
consumption of 60% of the rate point. This is very useful for installations that
run 24 hours a day.
CN1 and CN2
7
Current control demand 70%
This signal allows to regulate current consumption and establish an average
consumption of 70% of the rate point. This is very useful for installations that
run 24 hours a day.
CN1 and CN2
8
Current control demand 80%
This signal allows to regulate current consumption and establish an average
consumption of 80% of the rate point.This is very useful for installations that
run 24 hours a day.
CN1 and CN2
9
Current control demand 100%
This signal allows to regulate current consumption and establish an average
consumption of 100% of the rate point. This is very useful for installations
that run 24 hours a day.
CN1 and CN2
10
No setting application
No setting
—
Output signals
Ind.
Output signal
Application
Port
0
No setting application
No setting
—
01
Operation signal
This signal allows to pick up the machine’s operation signal. This is very
useful to start up additional systems such as humidifiers, fans and other ad-
ditional air-conditioning systems.
CN7
02
Alarm signal
This signal picks up the machine’s alarm. This is very useful to warn that an
alarm has been tripped.
CN7
03
Compressor ON signal
This single allows to pick up the compressor’s operation signal. It is very
useful for checking signals during remote-control operation and for the
interlock of the outdoor unit.
CN7
04
Defrost operation signal
This signal allows to pick up the defrosting of the unit. This is very useful to
know how the indoor unit is operating if there is an abnormal situation.
CN7
N O T E
Do not set same function to multiple input port. If set, the higher input terminal number will be cancelled.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......