2. Unit Installation
21
SMGB0079 rev.0 - 01/2013
2
Outlet Side Blocked
Upper Side Open
Single Installation
Multiple Installation (Two units or more)
Allow 100 mm of space between units. Both right and left sides shall be
open.
Be sure to use the fan direction guide. Leave open both right and left
sides.
Be sure to use the fan direction guide. Allow 100 mm of space between
units. Leave open both right and left sides.
No more than 2 units for multiple installation.
The length A is as shown in the following table:
L
A
0 < L ≤ 1/2H
600 or greater
1/2H < L≤ H
1400 or greater
When L > H use a base for outdoor unit to make L ≤ H.
Close the base not to allow the outlet air bypassed.
Lateral Side Blocked
Upper Side Open
Single Installation
Upper Side Blocked