8. Troubleshooting
211
SMGB0079 rev.0 - 01/2013
8
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Decrease of Discharge
Gas Superheat
Ref. cycle is different from the electrical system
Check ref. cycle and the
electrical system
Repair wiring
Overcharged Refrigerant
Measure pressure
Correctly charge refrigerant
Faulty Expansion Valve
Check expansion valve *1)
Replace expansion valve if
faulty
Faulty PCB
Fault
Replace PCB and check
operation
Replace PCB if faulty
Disconnected Wires for
Ex.Valve Control
Check connections.
Repair wiring connections
Faulty Discharge Gas
Thermistor
Fault
Measure resistance.
Replace thermistor if faulty
Incorrect Mounting
Check mounting state
.(See “Alarm Code 08”.)
Correctly mount thermistor.
Incorrect Connection
Check connections.
Remove looseness,
replace connector or repair
connections.
N O T E
• *1) Refer to section
Procedure of checking other main parts,
in part “Checking procedure for the electronic
expansion valve”.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......