10. Servicing
331
SMGB0079 rev.0 - 01/2013
10
Removing other electrical components
1
Remove the pipe cover following
Removing pipe cover
.
2
Remove 3 fixing screws and remove the upper cover.
3
Remove the electrical box cover.
4
Removing Electrical Components.
Remove the fixing screw and remove the reactor.
• To mount components be sure to match the wiring connection with the mark band codes.
1
2
3
4
5
6
1. Electrical box cover.
2. Partition plate.
3. Fuse.
4. Electrical box.
5. Reactor.
6. See the note.
N O T E
• The PCB cannot be removed from the electrical box. To replace PCB the entire electrical box must be replaced.
• DO NOT touch electrical components while the LED1 (Red) is ON to avoid electrical shock. Wait until the LED
turns off.