8. Troubleshooting
186
SMGB0079 rev.0 - 01/2013
8.1.3 Abnormal transmission between the remote control switch and the indoor unit
•
RUN LED on the remote control switch:
Flickering every 2 seconds.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Disconnection or insufficient contacting of the remote control cable
Check the cable and the connec-
tions
Repair the cable or connect the
cable
Failure of the remote control switch
Check the remote control switch
by means of the self-check mode
*1)
Replace the remote control switch
if the remote control switch is faulty
Failure of PCB (in the indoor unit
and the remote control switch)
Disconnected wire to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB by means of the self-
check mode *2)
Replace PCB if it failed
N O T E
•
*1): Refer to section
Self-checking of the remote control switch
.
•
*2): Refer to section
Self-checking procedure of PCB by means of the Remote Control Switch
.
8.1.4 Abnormal operation of the devices
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
RUN LED is ON and
the LCD is indicated.
However, the system
does not operate (For
example, the indoor
fan, the outdoor fan or
the compressor does
not operate)
Failure of the indoor unit
fan motor
Disconnected coil
Measure the coil resistance by
means of the tester
Replace the Indoor unit fan
motor
Burnt-out coil
Measure the insulation resist-
ance
Failure of the outdoor
unit fan motor
Disconnected coil
Measure the coil resistance by
means of the tester
Replace the outdoor unit fan
motor
Burnt-out coil
Measure the insulation resist-
ance
Failure of the magnetic
switch for the outdoor
unit fan motor
Insufficient contacting
Measure the voltage between
the contacting parts
Replace PCB for the outdoor
unit
Failure of the comp. motor
Measure the resistance be-
tween two wires
Replace the compressor
Failure of the comp.
Check for an abnormal sound
from the Comp.
Failure of the magnetic
switch for comp.
Insufficient contacting
Check that the magnetic switch
activates correctly or not
Replace the magnetic switch
Failure of one of PCBs
Disconnected wiring
to PCB
Check the connections
Correctly connect the wiring
Failure of PCB
Check PCB by means of the
self-check mode *1)
Replace PCB if it failed
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......