8. Troubleshooting
228
SMGB0079 rev.0 - 01/2013
Phenomenon
Cause
Check item
Action
(Turn OFF main switch)
Activation of High Pressure
Switch due to Excessively High
Discharge Pressure during
Cooling Operation
Insufficient Air Flow to Heat
Exchanger of Outdoor Unit
Clogging of Heat Exchanger?
Remover clogging
Check for dust on air filter
Remove dust
Check the service space
Secure service space
Check for outdoor fan speed
Replace fan motor if faulty
Excessively High Temp. Air to
Outdoor Unit Heat Exchanger
Check for hot air near the ceiling
Make good circulation
Check for short circuited air
Remove short-circuited air
Check for other heat source
Remove heat source
Faulty High
Pressure Switch
Faulty Pressure
Switch
Measure discharge pressure.
Check continuity after decreasing
of pressure
Replace it if faulty
Insufficient
Contacting
Measure resistance by tester
Repair looseness.
Replace connector
Incorrect
Connection
Check connections
Repair connections
Overcharged Refrigerant
Check cycle operating temp.
Charge refrigerant correctly
Mixture of Non-Condensable Gas in
Refrigerant Cycle
Check ambient temp. and
pressure
Recharge refrigerant after vacuum
pumping
Clogging of Discharge Piping
Check for clogging
Remove clogging
Faulty or Malfunction of Expansion
Valve
Check for clogging
Remove clogging
Check connecting wiring and
connectors
Replace connector
Check operating sound from coil
Replace coil
Check discharge gas thermistor
Replace thermistor
Check attaching state of discharge
gas thermistor
Reattach thermistor
Liquid Line Stop Valve or Gas Line
Stop Valve are not in Operation
Check stop valves
Fully open stop valve
Locking up Outdoor Unit Expansion
Valve Closure
Check expansion valve actuation
Replace outdoor
expansion valve
N O T E
This alarm code is indicated when the outdoor unit protective device is activated by high discharge pressure du-
ring cooling operation. Accordingly, when this alarm code is indicated, there is high possibility of high pressure
switch actuation and the above troubleshooting actions are based on such cases.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......