12. Maintenance notes
456
SMGB0079 rev.0 - 01/2013
12.1 General notes
12.1.1 Checking the power source and the wiring connection
Check the following items in the case of abnormal operation:
No.
Check item
Procedure
1
Is the breaker of the fuse cut
out?
Check the secondary voltage of the breaker and the fuse by means of a tester.
2
Is the secondary power source
on the transformer correct?
Disconnect the secondary side of the transformer and check the voltage by means of a tester.
Indoor unit
transformer
Secondary
side
Primary side
220, 230 or
240 V
Circuit and voltage
12 V
12 V
3
Is the wiring loosened or inco-
rrectly connected?
Check the wiring connection on the PCB.
•
Thermistor connectors
•
Connector of the remote control cable
•
Connector of the transformer
Each connector in a high-voltage circuitCheck the connectors according to the
electrical wiring
diagram.
12.1.2 Burnt-out compressor due to an insufficient refrigerant charge
Question and answer for the field work
Example 1: Burnt-out compressor due to an insufficient refrigerant charge
Phenomenon
After commissioning the alarm code “08” sometimes occurred and the compressors were burnt out after operating for two
months.
Cause
The refrigerant piping work was performed during the summer season. The additional refrigerant was not sufficiently
charged from the discharge gas side.
This insufficient refrigerant charge resulted in the overheating of the discharge gas and the oil deterioration which was
finally due to the separated operation despite the alarm code “08”.
Countermeasure
1
The compressor was replaced with a new compressor.
2
The correct refrigerant amount was charged according to the refrigerant piping length and the connected indoor units.
Remarks
Additional refrigerant charge: Open the liquid stop valves slightly when you charge the additional refrigerant from the
check joint of the liquid stop valves (the discharge gas side) during the cooling process. If the liquid stop valve is fully open
it is difficult to charge the additional refrigerant. Do not charge the refrigerant from the gas stop valve.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......