8. Troubleshooting
272
SMGB0079 rev.0 - 01/2013
Cause of indoor unit stoppage (
dA
)
Indication
Contents
00
Operation OFF, Power OFF
10
Demand thermo OFF:
32
30
28
26
24
22
20
5
10
15
20
25
(
o
C)
(
o
C)
29
23
23
26
21
19
17
Thermo-OFF Temperature Area
Temperature Area in Heating Operation
Outdoor Temperature
Restart
Temperature Area
Forced Stoppage
Temperature Area
Air Inlet
Te
mp. of Indoor Unit
01
Thermo-OFF
02
Alarm
03
Freeze protection overheating protection
05
Instantaneous power failure at outdoor unit
06
Instantaneous power failure at indoor unit
07
Stoppage of heating operation due to high outdoor
air temperature
10
Demand thermo OFF
13
Retry for Pd increase prevention
15
Vacuum/discharge gas temperature increase retry
16
Retry due to discharge gas SUPERHEAT decrease
17
IPM error retry, instantaneous over current of in-
verter retry, electronic thermal activation of inverter
retry, abnormal current sensor of inverter retry
18
Retry due to inverter voltage decrease
Retry due to
Inverter Over
voltage
Retry due to inverter transmission abnormality
19
Other retry
21
Forced Thermo-OFF
22
Outdoor hot start control
24
Thermo-OFF during energy saving operation mode
26
Retry due to high pressure decrease
28
Cooling air discharge temperature decrease
33
Forced Thermo-OFF
34
Forced Thermo-OFF
35
Retry due to abnormal operating mode
(Reversing valve switching failure)
N O T E
• The cause code for indoor unit stoppage is not always “
02
“ (Alarm) during stoppage by the abnormality.
If the unit is under Thermo-OFF by other cause of stoppage before ”
02
“ (Alarm) occurs, the previous cause
code for indoor unit stoppage remains.
• When the transmitting between the inverter PCB and the outdoor unit PCB1 is disconnected for 30 seconds,
the outdoor micro-computer will be reset. Accordingly when the alarm code “
04
” (Abnormal Transmitting
between Inverter PCB and Outdoor Unit PCB1) occurs, the cause code for indoor unit stoppage may be indi-
cated “
05
”.
• When the transmitting between the indoor unit and the outdoor unit is disconnected for 3 minutes, the indoor
micro-computer will be reset. Accordingly when the alarm code “
03
” (Abnormal Transmitting between Indoor
Unit and Outdoor Unit) occurs, the cause code for indoor unit stoppage may be indicated “
06
”.
• For twin, triple and quad combination, if the cause code for indoor unit stoppage “
21
” is indicated, check the
cause of stoppage for other indoor units.
• Cause code for indoor unit stoppage “
22
” is indicated when it is forced thermo-OFF during compressor pre-
heating for RAS-12HN(P/C) models.
Summary of Contents for EV-1.5N1
Page 2: ......
Page 4: ... II ...
Page 26: ......
Page 100: ......
Page 144: ...5 Control System 130 SMGB0079 rev 0 01 2013 5 4 2 Dry operation Continues in the next page ...
Page 148: ...5 Control System 134 SMGB0079 rev 0 01 2013 5 4 4 Automatic cooling and heating operation ...
Page 158: ......
Page 196: ......
Page 212: ...8 Troubleshooting 198 SMGB0079 rev 0 01 2013 ...
Page 215: ...8 Troubleshooting 201 SMGB0079 rev 0 01 2013 8 ...
Page 323: ...9 Spare parts 309 SMGB0079 rev 0 01 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211B ...
Page 332: ......
Page 452: ......
Page 479: ......