Ultra Heat GMV VRF Technical Service Manual INSTALLATION
71
Step 2: Turn on the valves for the liquid and gas pipes of each module completely.
Step 3: Make the system to run in commissioning mode via the commissioning software or the main
board of the ODU. (For details, see the description on commissioning.)
Step 4: When the commissioning step goes to refrigerant perfusion, turn on the valve of the
refrigerant tank and perfuse the remaining quantity.
Step 5: After all refrigerant is perfused, turn off valve of the refrigerant tank and wait till
commissioning is automatically is completed for the system.
Step 6: Remove the pressure gauge to finish refrigerant perfusion.
Because R410A is a mixture of refrigerant, therefore, it must be charged in a liquid form.
Otherwise, unit will not work stably and effectively.
Do not expose the R410A refrigerant tank to direct sunlight. Otherwise, the internal pressure may
get too high and cause explosion.
Pipeline for the R410A refrigerating system must have relevant valid certificates.
During welding, avoid overheating the pipeline.
System must not filled with refrigerant other than R410A.
Pipe to be vacuumed : gas pipe, water pipe, common pipe
If the refrigerant amount is not exact, it may not operate properly.
If additionally bottled refrigerant amount is over ±10%, condenser burning or insufficient indoor
unit performance may be caused.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...