Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL
204
exceeds 100m, please use a repeater to enhance communication; all gateways must be connected to
the LAN interface of router.
L5: L5 as shown in the figure is the power line; power line shall be arranged strictly according to
network 1 or network 2. In network 1, the indoor units and outdoor units in one system share one electric
meter. In network 2, all indoor units in one system share one electric meter and all outdoor units share
one electric meter.
Notice:
1) In one CAN2 network, a maximum of 16 air conditioning systems and 255 IDUs are allowed. If
exceeded, the CAN2 network should be divided into two.
2) One gateway can be connected to only one CAN2 network.
3) One VRF monitoring system can be connected to 16 gateways in maximum.
4) The way of communication among units and gateway is the same with network 3 (without billing
function, disconnecting electric meter).
2 HARDWARE
2.1 List of Parts
Name
Type
BOM
Supply Range
Remark
Gateway
Monitoring part
FE22-41/BEF(MCB)
MC20001450
SC
Interconnect with VRF monitoring
system.
Optoelectronic
isolated repeater
Optoelectronic isolated
repeater RS485-W
EN02200010
Optional
For 485 communication bus, set
a repeater every 800 m; for
electric meter, add a repeater
every 30 electric meters.
Repeater
/
/
Prepared by
users
This repeater is required only
when the length between
gateway LAN output and PC
exceeds 100m.
Control cabinet
/
/
Prepared by
users
2.2 Gateway
2.2.1 Functions
Long-distance monitor gateway converts CAN, RS485 bus data into TCP/IP and communicate with
Ethernet through common router, so as to achieve central monitoring, billing, error reminding functions.
(1) Interface Drawing
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...