Ultra Heat GMV VRF Technical Service Manual MAINTENANCE
118
2) Faults in the current detection circuit drive of compressor (ODU fault PC) and out-of-step
protection of compressor (ODU fault P9)
3) AC over-current protection (ODU fault P5) and IPM module over-current protection faults
(ODU fault P6)
Attachment: How to check whether the IPM module is damaged
a. Preparation: Find a digital multi-meter and switch it to the diode. Remove U, V and W cables of
the compressor from the drive board two minutes after the system is powered off. Make sure that it is
tested at least two minutes after the system is powered off. Then put the multi-meter to diode test
step.