3.2.1 Introduction to function buttons
When function buttons are used to set functions for outdoor unit, the cover of electric box and panel
must be assembled well. Setting can only be done through the maintenance window. Otherwise, electric
shock may occur.
The main board AP7 of the ODU consists of six function buttons:
Function Button Name and Meaning
Button
Code
Function Meaning
SW1
FUNCTION
Indicates the function button, used for function settings.
SW2
+
Indicates the upward selection button.
SW3
-
Indicates the downward selection button.
SW4
ENTER
Indicates the confirmation button.
SW5
BACK
Indicates the return button, used to return to the upper-level menu.
SW6
Reserved function and meaningless currently.
3.2.2 Introduction to functions
Function
Code
Function Name
Function Meaning
Remark
Ft
Test run mode
Used for running before factory, enable ODU controller
and parts to work fluently.
Control (CU)
function can be set
as ON or OFF
according to actual
situation.
A8
Aftersales vacuuming
mode
Automatically enables all electronic expansion valves and
electromagnetic valves during maintenance to guarantee
vacuum processing in all pipelines.
A2
Refrigerant recovery
operation
Fully or partially recovers refrigerants in a faulty module
or IDU pipeline according to the system pressure after
automatic startup during maintenance.
A3
Forcible defrosting
operation
Forcibly enables ODU defrosting operation.
NH
Suction temperature
Displays the value of suction temperature.
Display (DI)
function is to
display the value of
ODU parameter.
NP
Discharge temperature
Displays the value of discharge temperature.
NW
Environment temperature
Displays the value of environment temperature.
PL
Low pressure
Displays the value of low pressure.
PM
Middle pressure
Displays the value of middle pressure.
PH
High pressure
Displays the value of high pressure.
N1
Online ODU quantity
Displays the number of online ODUs.
N9
Online IDU quantity
Displays the number of online IDUs.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...