Ultra Heat GMV VRF Technical Service Manual MAINTENANCE
153
5. Install a new oil
separator.
●Weld the four pipe joints with the oil separator.
During welding, charge nitrogen into the pipes.
The pressure should be controlled within
0.5±0.1 kgf/cm
2
(relative pressure).
Note: Avoid nearby parts from being burnt
during welding.
●Screw the oil separator.
●Tighten the electric heating belt.
6. Fix and wire the electric
box.
●Put the electric box back to original position
and screw it.
●Connect all lines.
7. Check and install the front
panels.
●Check various parts and connecting lines.
●If no problem is found, hook the front panels
and tighten the screws.
Gas/liquid separator
Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.
Step
Diagram
Operation Procedure
1. Loosen the hooks at the
bottom of the electric box
and the screws.
●Use a screwdriver to unscrew the upper and
lower front panels.
●Lift the front panels in order to take it out.
Note: Both the upper panel and lower panel are
fixed with two fasteners respectively to connect
to the side panels.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...