Ultra Heat GMV VRF Technical Service Manual INSTALLATION
44
1.3.4 Pipe connection
1.3.4.1 Flaring connection
The refrigerant pipes and IDUs are connected by using the flare opening. Therefore, the quality of
flaring connection must be ensured. The flaring depth of the bell mouth cannot be smaller than the
caliber. The flaring direction must face towards the direction of medium flow. Use two torque wrenches to
fasten the connection.
1.3.4.2 Socket welding
The gap between socket components should be proper to ensure that the connection will not loose
from the friction surface. The flaring direction of the socket component must face towards the direction of
medium flow .During pipe connect, protect the braze welding part according the length specified below:
A: External Diameter of the Pipe
B: Minimum Insertion Depth
D-A: Gap between Pipes
mm
inch
mm
inch
mm
inch
6.35
1/4
6
0.24
0.05-0.21
0.002-0.008
9.52
3/8
7
0.28
12.7
1/2
15.8
5/8
8
0.32
0.05-0.27
0.002-0.01
19.05
3/4
10
0.39
22.2
7/8
25.4
1
28.6
1-1/8
12
0.47
0.05-0.30
0.002-0.012
31.8
1-1/4
38.1
1-1/2
19
0.75
0.15-0.35
0.006-0.014
44.5
1-3/4
1.3.4.3 Bell socket welding
The bell socket welding is another form of socket welding. It uses the sleeve or pipe in a larger size
for welding. The insertion depth cannot be smaller than that required by socket welding.
1.3.4.4 Flange connection
The pipes with large caliber and the devices are always connected by using a flange, which must be
clean and intact. Before installation, apply lubricant on the surface of the flange. Two flanges must be
symmetrical. Fasten with screws at the diagonal direction to avoid inclination.
1.3.5 Welding protection
Aerate with nitrogen before and during welding and keep aerating for 30s after the welding is
finished.
Equip a pressure regulator valve to the nitrogen cylinder.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...