Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL
226
communication lines and DIP settings.
4.4 Communication Debug between Gateways and Gree VRF Monitoring
System
After installing the software successfully, it is starting with the system by default. If the users need to
start up or shut down the software by themselves, they can find the menu of this software in start menu
of the system.
Step 1: Click AutoRun, the software will start up with the system (PC).
Step 2: If the G module is connected directly to the computer using the network cable, set IP
address of PC to 192.168.0.x, with x>2. And set address mask to 255.255.255.0. Then input server IP
address in address field of browser (for current unit, input
Step 3: Log in to VRF Monitoring System. For the first usage or after resetting the system, check
equipment connection status in main interface (click ―VRF monitoring system‖ on the left corner to enter
the main interface), to make sure G module quantity and IDU & ODU quantity displayed on the page are
consistent with actual quantity.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...