Ultra Heat GMV VRF Technical Service Manual COMMISSIONING OPERATION
80
For example, if A8 function is selected in step 5, then press "SW2 (+)" or "SW3 (-)" to set data
(LED3). The master unit is displayed as follows:
LED1
LED2
LED3
Function Code
Display Mode
Confirmation
Display Mode
Current Data
Display Mode
A8
On
/
/
OF
Blinking
A8
On
/
/
On
Blinking
Next, if
―On‖ data is selected, then press "SW4" to confirm it. The master unit is displayed as
follows:
LED1
LED2
LED3
Function Code
Display Mode
Confirmation
Display Mode
Current Data
Display Mode
A8
On
=
On
On
On
Note: othe
r CU function’s setting way is the same with ―A8‖. ―/‖ means nothing displayed.
On the master unit, press "SW5" to return to the upper level if there are two levels of menu. And
press "SW5" long to cancel the setting function status.
Step 6: When
―DI‖ function displays, press "SW4" on the master unit, then the master unit is
displayed as follows:
LED1
LED2
LED3
Function Code
Display Mode
Confirmation
Display Mode
Current Data
Display Mode
NH
Blinking
/
/
Parameter value
On
Then users can select corresponding functions by pressing "SW1" on the master unit, including:
LED1
LED2
LED3
Function Code
Display Mode
Confirmation
Display Mode
Current Data
Display Mode
NH
Blinking
/
/
Parameter value
On
NP
Blinking
/
/
Parameter value
On
NW
Blinking
/
/
Parameter value
On
PL
Blinking
/
/
Parameter value
On
PM
Blinking
/
/
Parameter value
On
PH
Blinking
/
/
Parameter value
On
N1
Blinking
/
/
Parameter value
On
N9
Blinking
/
/
Parameter value
On
LED3 displays the parameter value. By default, the ODU temperature values unit are
℃
, and
pressure values unit are 0.01MPa.
For example:
Parameter Code
Parameter Name
Unit
Remark
NH
Suction temperature
°C
If LED3 shows 12, it means suction temperature is 12
℃
.
NP
Discharge temperature
°C
If LED2 shows 1 and LED3 shows 04, it means discharge
temperature is 104
℃
.
NW
Environment temperature
°C
If LED2 shows - and LED3 shows 10, it means
environment temperature is -10
℃
.
PL
Low pressure
0.01MPa
If LED3 shows 95, it means low pressure is 0.95MPa.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...