Ultra Heat GMV VRF Technical Service Manual COMMISSIONING OPERATION
94
Code
Display status
code
Display status
Code
Display status
08_Confirm
debugging startup
db
Light
08
Light
AP
Blink
If it’s confirmed, press SW4 confirmation button. And if AE has been chosen in step 12, unit will
display as below and start next progress. (Of course, if AL has been chosen in step 12, LED3 will display
AL and start next progress.)
——
Debugging code
Progress code
Status code
progress
LED1
LED2
LED3
Code
Display status
code
Display status
Code
Display status
08_Confirm
debugging startup
db
Light
08
Light
AE
Light
Step 14: after unit is confirmed to start debugging, system select cooling/heating mode according to
ambient temperature.
A If cooling mode is selected, relevant display is as below:
——
Debugging code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
09_Cooling
debugging
db
Light
09
Light
UC
Light
Debugging is enabled in cooling mode
(debugging mode, auto-selected by
system).
db
Light
09
Light
Error
code
Light
ODU Error occurs during debugging in
cooling mode.
db
Light
09
Light
XXXX/d5
Light
System detects error in indoor pipeline.
XXXX is IP of the faulted IDU. 3s later,
error code d5 is displayed. For
example, IDU no. 100 has d5 error,
then LED3 displays like this: 01 (2s
later) 00 (2s later) d5, and repeat
again.
B If heating mode is selected, relevant display is as below:
——
Debugging code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
10_Heating
debugging
db
Light
09
Light
UH
Light
Debugging is enabled in heating mode
(debugging mode, auto-selected by
system).
db
Light
09
Light
Error
code
Light
ODU Error occurs during debugging in
heating mode.
db
Light
09
Light
XXXX/d5
Light
System detects error in indoor pipeline.
XXXX is IP of the faulted IDU. 3s later,
error code d5 is displayed. For
example, IDU no. 100 has d5 error,
then LED3 displays like this: 01 (2s
later) 00 (2s later) d5, and repeat
again.
Step 15: if there’s no error during operation for about 30min, system will automatically confirm that
debugging is finished and then stop. After debugging is finished, some functions can be set up according
to project’s actual needs. For specific details, please refer to System Functions Setup. If no special
requirements, skip this step.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...