Ultra Heat GMV VRF Technical Service Manual MAINTENANCE
124
1.1.3 Cautions on replacement of master IDU AP1
If the AP1 of the master IDU needs to be replaced, after the IDU is powered on,
―No master IDU
(L7)
‖ or ―Project number conflict (C5)‖ alarm may be reported.
(1) Troubleshoot for
―no master IDU (L7)‖ fault
Method 1: If the IDU is configured with wired control, stop the IDU (except for lock mode) and press
and hold the
―MODE‖ button for 5 seconds to enter setting mode. After setting, the ―Master‖ icon will be
highlighted and the wired control buzzer will beep once.
Method 2: If the IDU is configured with lamp board or wired control, set to fan mode, 30°C/86°F,
and press and hold
―-― and ―+‖ consecutively three times within 5 seconds. The IDU and wired control
will identify it as a master IDU setting command, and show
―set master IDU success (UC)‖ (5 seconds)
and highlight the
―Master‖ icon respectively.
Method 3: If the IDU is configured with the Debugger, set the IDU to master IDU through this
software.
(2) Troubleshoot for
―project number conflict (C5)‖
If this fault occurs, the number of the new AP1 is identical to that of a unit within the network.
Manually change it to the original number of the faulty AP1 or a unique number. There are three
methods to change project number:
Method 1: If the IDU is configured with wired control, set P42 to a new project number.
Method 2: If the IDU is configured with lamp board, use the special control YV1L1 to set P42 to a
new project number.
Method 3: If the IDU is configured with the Debugger, configure a new project number through this
software.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...