Ultra Heat GMV VRF Technical Service Manual INSTALLATION
38
(b)
(2) Select appropriate pipe between o
utdoor unit and the first indoor branch (―L‖) as per the pipe
size of outdoor unit. Pipe size of basic outdoor module is shown as follows:
Basic module
Pipe between outdoor unit and the first indoor branch
Gas pipe mm(inch)
Liquid pipe mm(inch)
GMV-V72W/A-F(U)
Φ28.6(1-1/8)
Φ9.52(3/8)
GMV-V96W/A-F(U)
Φ28.6(1-1/8)
Φ9.52(3/8)
(3)
Branch selection of mode exchanger (―A1, A2, A3‖)
Select branch of mode exchanger as per total capacity of downstream indoor unit(s). Please refer to
the following table.
R410A refrigerant system
Total Capacity of the Downstream Indoor Unit X(Btu/h)
Model
Y-type Branch Pipe
C≤68000
FQ01A/A
68000
<
C≤102000
FQ01B/A
102000
<
C≤239000
FQ02/A
239000
<
C
FQ03/A
T-type Branch Pipe
C≤136000
FQ014/H1
136000
<
C≤232000
FQ018/H1
232000
<
C
FQ018/H2
(4) Piping size among upstream branches (
―b, e‖)
Total rated capacity of downstream
indoor units: X(Btu/h)
Size of connection pipe between branches
Gas pipe mm(inch)
Liquid pipe mm(inch)
X≤17100
Φ12.7(1/2)
Φ6.35(1/4)
17100
<
X≤48500
Φ15.9(5/8)
Φ9.52(3/8)
48500
<
X≤72000
Φ19.05(3/4)
Φ9.52(3/8)
72000
<
X≤96000
Φ22.2(7/8)
Φ9.52(3/8)
96000
<
X≤144000
Φ28.6(1-1/8)
Φ12.7(1/2)
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...