Ultra Heat GMV VRF Technical Service Manual MAINTENANCE
149
3.Disassemble the four-way
valve.
Use a screwdriver to unscrew accessories of
the four-way valve. Remove the accessories.
●Heat the connecting pipes of the four-way
valve by acetylene welding and then remove
the pipes.
●Record the direction of the valve and position
of the pipe joints.
Note: Avoid nearby parts from being burnt
during welding.
4. Remove the four-way
valve.
●Remove the four-way valve from the pipeline.
5. Install a new four-way
valve.
●Put the valve in a proper position.
●Weld the valve with the pipeline.
●Before welding, cover the valve with wet cloth
to avoid internal slide from being burnt and
prevent water from flowing in the pipeline.
●During welding, charge nitrogen into the
pipes. The pressure should be controlled
within 0.5±0.1 kgf/cm2 (relative pressure).
6. Fix and wire the electric
box.
●Put the electric box back to original position
and screw it.
●Connect all lines.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...