Ultra Heat GMV VRF Technical Service Manual INSTALLATION
28
(4) Anti-monsoon installation requirements for unit connecting exhaust duct:
(5) Considering snow in outdoor unit installation
(6) During the installation of the ODU, induced and exhaust pipes must be connected. In addition,
the aperture opening rate of shutters must be at least 80%, and the angle between the shutters and the
horizontal plane should be less than 20°. Requirements for installing exhaust air duct are as follows:
1) Basic requirement for connecting an ODU to static pressure ventilating duct
When an ODU needs to be connected to the static pressure ventilating duct, the ventilating duct
must be reasonably designed. The pressure loss caused by the ventilating duct must be calculated. In
addition, a proper type of ventilating duct is necessary. To connect he static pressure ventilating duct to
the ODU, three basic parts are required:
①
ODU.
②
Canvas.
③
Steel-plate ventilating duct.
The ODU must be interconnected with the ventilating duct through canvas to prevent abnormal
vibration and noise generated by the steel-plate ventilating duct. The joint part must be tightly sealed
with tin foil to avoid air leakage.
2) Preparations for connecting an ODU to static pressure ventilating duct
a). The ODU is installed properly based on the unit installation requirement.
b). The steel-plate ventilating duct is designed based on the unit and engineering requirement, and
is installed properly according to the engineering standards.
c). Based on the unit dimensions and the size of steel-plate ventilating duct, prepare materials such
as canvas casing, tin foil, steel bar and tapping screw, as well as tools such as hand-operated electric
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...