Ultra Heat GMV VRF Technical Service Manual MAINTENANCE
136
well. This is to avoid abnormality from happening inside the gas/liquid separator, and affecting system
safety and reliability.
Put the gas/liquid separator on a chassis and connect the inlet pipe of the gas/liquid separator with
the outlet pipe. Then, connect the pipe to a nitrogen source. The nitrogen source can be connected
based on actual situation, for example, you can add a bypass interface or directly connect the nitrogen
source to the inlet/outlet pipe. If the pipe is big, cover it with tape as well. Make sure nitrogen can
smoothly flow through the gas separator.
Step 9: Install a new oil separator.
The original oil separator, if is found to have no impurities or other objects, can be used further
more. This part serves as a container and it does not have complex structure. However, if it contains
impurities or other objects, replace it. This is because a dirty oil separator cannot be thoroughly
cleaned.
Step 10: Install a new compressor.
If it is a inverter compressor that needs replacement
1
、
Put the gas/liquid
separator
on
a
proper position.
2
、
Connect the inlet
pipe of the separator
with the outlet pipe.
3
、
Weld the pipes
together.
4
、
Screw the
separator onto the
chassis.
1
、
Put the oil
separator
on
a
proper position.
2
、
Weld
the
connecting pipes of
the oil separator.
3
、
Screw the oil
separator.
4
、
Weld the oil
pipes.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...