Ultra Heat GMV VRF Technical Service Manual INSTALLATION
63
One wired controller controlling one IDU Two wired controllers controlling one IDU
One wired controller controlling multiple IDUs
Two wired controllers controlling multiple IDUs
When two wired controllers control multiple IDUs, the wired controllers can be connected to any IDU
which is in the same series. Set one of the two wired controllers to the secondary wired controller. The
number of IDUs controlled by the two wired controllers cannot exceed 16. All connected IDUs must be in
the same network.
The secondary wired controller can be set in start-up or shut down mode.
(1) Press the
―FUNCTION‖ button for 5 seconds on the wired controller to be set as the secondary
wired controller. The temperature area displays
―C00‖. Continue to press the ―FUNCTION‖ button for 5
seconds, the parameter setting interface is displayed and the temperature area displays
―P00‖.
(2) Select code P13 by pressing
or
. Press the
―MODE‖ button to switch to parameter
value setting. When the parameter value flickers, select code 02 by pressing
or
. Then press
the ―ENTER/CANCEL
‖
button to finish setting.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...