Ultra Heat GMV VRF Technical Service Manual MAINTENANCE
132
After the compressor and oil separator are removed, check oil quality. If oils are contaminated,
replace the compressor, oil separator, and gas/liquid separator. If oil changes to black, check oils of
other modular units. The check procedure is similar to the preceding.
Note:
Before replacing the faulty compressors, make sure to block their openings with tapes. They
should be kept intact for further analysis.
Step 5: Check system parts.
If system oil is contaminated, check unit parts, including oil separator, gas/liquid separator, and
storage tank.
(1) Check oil separator.
Remove the oil separator. For the removal procedure, refer to step 4. Tilt the separator to draw oil
out into a container. Block the container for further factory inspection.
(2) Check gas/liquid separator.
After the gas/liquid separator is taken out, check whether it contains impurities. The check
procedure is as follows:
1
、
Weld the oil
pipe.
2
、
Weld the inlet and
outlet pipes of the
oil separator.
3
、
Unscrew the oil
separator.
3
、
Remove the
gas/liquid pipe.
1
、
Weld the inlet and
outlet pipes of the
gas separator.
2
、
Unscrew the
gas/liquid pipe.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...