Ultra Heat GMV VRF Technical Service Manual UNIT INTRODUCTION
8
2 INTERNAL PIPING DESIGN OF THE UNITS
2.1 Piping Diagram of GMV-V72W/A-F(U)
、
GMV-V96W/A-F(U)
2.2 Names and main functions of components
No.
Name
Main Function
1
Compressor
Adjusts its own rotational speed based on the actual requirement of the
system to implement capacity control.
2
Compressor heat tape
Maintains a proper oil temperature in the compressor when the compressor
is in standby status, ensuring the reliability during compressor startup.
3
Exhaust pipe temperature sensor of
compressor
Detects a compressor's exhaust gas temperature for compressor control
and protection.
4
High-pressure circuit breaker
Protects a compressor by sending feedback signal to stop the system when
the compressor's discharge pressure exceeds the operating value of
high-pressure circuit breaker.
5
Oil extractor
Separates the gas and oil in the system to ensure compressor reliability.
6
One-way valve
Prevents high-pressure gas from entering the compressor and fast balances
the suction pressure and discharge pressure in a compressor.
7
High-pressure sensor
Detects the high pressure value in the system in real time mode for
compressor protection and other control functions.
8
Four-way valve 1
Used for the switching between the cooling and heating functions of system
IDU.
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...