Ultra Heat GMV VRF Technical Service Manual MAINTENANCE
127
NOTE: You can infer from the preceding figures the current of the compressors operating at other
frequency bands.
Step 2:
Check whether the compressor sounds sharp or rubs. Compare the sound of the faulty
compressor with that of normal ones.
Step 3:
Check whether the electric expansion valves of ODUs and the 4-way valves act, and
whether the oil return pipes and oil balance valves 1 and 2 are normal. Touch the pipelines next to the
return capillary tubes to check whether there is oil flowing.
Check method for each part:
(1) Electric expansion valve: This valve will reset for each power-on or power-off action. Touch the
valve and you will feel its vibration during the reset action. A crack sound will be heard as well.