Ultra Heat GMV VRF Technical Service Manual INSTALLATION
67
discharged.
(5) After vacuumization, turn off the regulator valve and keep for 1 hour. Ensure that the pressure of
the regulator valve does not increase.
2.2.2 Precautions
(1)
Before vacuum pumping, make sure that outdoor unit’s liquid valve and gas valve are completely
closed. Use vacuum pump to extract air inside indoor unit and connection pipe from the nozzles of liquid
valve and gas valve of outdoor unit, as shown in follow figure.
(3) Turn off the valve before powering off the vacuum pump.
(4) Keep vacuuming for 2 hours. The vacuum meets the requirement if the pressure displayed by
the vacuum gauge does not increase.
(5) The units parallel connected to the module also need to be vacuumized.