Ultra Heat GMV VRF Technical Service Manual MAINTENANCE
104
O
u
td
o
o
r
E
Outdoor ambient
temperature is
beyond normal
range
F
Malfunction of
casing top
temperature sensor
of compressor 1
Malfunction of
casing top
temperature
sensor of
compressor 2
Malfunction of exit
tube temperature
sensor of mode
exchanger
Malfunction of
inlet tube
temperature
sensor of mode
exchanger
J
b
Malfunction of
temperature sensor
of oil return 3
Malfunction of
temperature
sensor of oil
return 4
P
AC input voltage of
drive of inverter
compressor
H
AC input voltage of
drive of inverter fan
Deb
u
g
g
in
g
U
C
Communication
malfunction
between IDU and
the receiving lamp
Overflow
distribution of IP
address
Communication
malfunction
between mode
exchanger and
ODU
Malfunction of
network for IDU
and ODU of
mode exchanger
Communication
malfunction of
mode exchanger
Sta
tu
s
A
Long-distance
emergency stop
Emergency stop
of operation
Limit operation
Child lock status
Shielding status
n
Eliminate the
long-distance
shielding command
of IDU
Bar code inquiry
Length
modification of
connection pipe
of ODU
For example, when E4 is displayed on the ODU, find line E and column 4 in the above tables. The
fault is shown in the intersection of the line and column: High exhaust temperature protection.
2 ODU LEDS TABLE
On the master ODU AP7, there are three LEDS and the flashing meaning is:
Flicker
Times
Green
Red
Yellow
1
Drive board
Outdoor unit is always at ON status
Fan ON
2
Reservation
Reservation
Compressor ON
3
Reservation
Oil return
IPM Overcurrent for fan
4
PC monitor
Defrosting
IPM Overcurrent for compressor
5
Indoor unit 1
Limited frequency reduction for IPM temperature protection
Fan IPM protection
6
Indoor unit 2
Limited frequency reduction for PFC temperature protection
Compressor IPM protection
7
Indoor unit 3
Limited frequency reduction for AC current protection
PFC overcurrent
8
Indoor unit 4
Limited frequency reduction for power protection
PFC protection
9
Indoor unit 5
Limited frequency reduction for discharge temperature
protection
Low voltage protection
10
Indoor unit 6
Limited frequency reduction for low pressure protection
High voltage protection
11
Indoor unit 7
Limited frequency reduction for high pressure protection
Low pressure protection
12
Indoor unit 8
Malfunction of discharge temperature sensor of
compressor 1
High pressure protection
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...