Ultra Heat GMV VRF Technical Service Manual COMMISSIONING OPERATION
75
methods are as follows:
Outdoor Silent Mode Setting DIP Switch (S1)
DIP1
DIP2
Noise Range
0
0
Standard mode
1
0
Low noise mode
0
1
medium noise mode
1
1
superlow noise mode
The default factory setting is
―00‖.
On the DIP switch,
―ON‖ indicates ―0‖ status and the opposite direction indicates "1‖ status.
Note that the DIP switch should be independently set on each module.
After silent mode is set, unit
’
s cooling and heating capacity will be lowered correspondingly. Please be
noted.
3.1.2 Outdoor fan static pressure setting DIP switch (S2)
The outdoor fan static pressure setting DIP switch (S2) is used in special scenarios such as the unit
installation equipment room. In scenarios where air ducts are required to be connected, zero static
pressure (0 Pa), low static pressure (30 Pa), medium static pressure (50 Pa), and high static pressure
(82 Pa) can be set according to the design of air ducts. The setting methods are as follows:
Outdoor Fan Static Pressure Setting DIP Switch (S2)
DIP1
DIP2
Static Pressure Range
0
0
0 Pa/0in.W.G.
1
0
30 Pa/0.12in.W.G.
0
1
50 Pa/0.2in.W.G.
1
1
82 Pa/0.328in.W.G.
The default factory setting is
―00‖.
On the DIP switch,
―ON‖ indicates ―0‖ status and the opposite direction indicates "1‖ status.
Note that the DIP switch should be independently set on each module.
3.1.3 Centralized control address DIP switch (S3)
The centralized control address DIP switch (S3) indicates the centralized control address required
when different refrigerating systems are controlled in a centralized manner. The default factory setting is
"00000".
If it is not required to use centralized control between multiple refrigerating systems, this DIP switch
can retain the factory settings without being changed.
If it is required to use centralized control between multiple refrigerating systems, set the DIP switch
according to the following methods:
Summary of Contents for Ultra Heat GMV-V72W/A-F
Page 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Pump Series...
Page 22: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 17 CHAPTER 2 INSTALLATION...
Page 26: ...Ultra Heat GMV VRF Technical Service Manual INSTALLATION 21...
Page 105: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 100 CHAPTER 4 MAINTENANCE...
Page 116: ...Ultra Heat GMV VRF Technical Service Manual MAINTENANCE 111...
Page 180: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 175 CHAPTER 5 REMOTE CONTROL...
Page 206: ...Ultra Heat GMV VRF Technical Service Manual REMOTE CONTROL 201...
Page 239: ......
Page 240: ...Jf00303483...