5-318
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
TESTING
CHAPTER 5: SETTINGS
5
Table 5-44: Test mode operation
5.11.3 Phasor Measurement Unit test values
SETTINGS
TESTING
PMU TEST VALUES
PMU 1(6) TEST VALUES
TEST MODE
FUNCTION
In-service
LED
Test mode
LED
Critical fail
relay
TEST MODE
FORCING
Contact input and output behavior
Disabled
Unaffected
Off
Normal
No effect
Normal
Isolated
Off
On
De-energized No effect
Contact outputs disabled
Forcible
Off
Flashing
De-energized Off
Normal
On
Controlled by forcing features
On restart, the
TEST MODE FORCING
setting and the force contact input and force contact output settings revert to
their default states.
PMU 1
TEST VALUES
PMU 1 TEST
FUNCTION: Disabled
Range: Enabled, Disabled
PMU 1 VA TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
PMU 1 VA TEST
ANGLE: 0.00°
Range: –180.00 to 180.00° in steps of 0.05
PMU 1 VB TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
PMU 1 VB TEST
ANGLE: –120.00°
Range: –180.00 to 180.00° in steps of 0.05
PMU 1 VC TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
PMU 1 VC TEST
ANGLE: 120.00°
Range: –180.00 to 180.00° in steps of 0.05
PMU 1 VX TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
PMU 1 VX TEST
ANGLE: 0.00°
Range: –180.00 to 180.00° in steps of 0.05
PMU 1 IA TEST
MAGNITUDE: 1.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001
PMU 1 IA TEST
ANGLE: –10.00°
Range: –180.00 to 180.00° in steps of 0.05
PMU 1 IB TEST
MAGNITUDE: 1.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001
PMU 1 IB TEST
ANGLE: –130.00°
Range: –180.00 to 180.00° in steps of 0.05
PMU 1 IC TEST
MAGNITUDE: 1.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001
PMU 1 IC TEST
ANGLE: 110.00°
Range: –180.00 to 180.00° in steps of 0.05
PMU 1 IG TEST
MAGNITUDE: 0.000 kA
Range: 0.000 to 9.999 kA in steps of 0.001