6-22
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
METERING
CHAPTER 6: ACTUAL VALUES
6
6.4.3 Synchrocheck
ACTUAL VALUES
METERING
SYNCHROCHECK
SYNCHROCHECK 1(6)
If synchrocheck or a setting is "Disabled," the corresponding actual values menu item does not display.
6.4.4 Tracking frequency
ACTUAL VALUES
METERING
TRACKING FREQUENCY
The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
setting in the
SETTINGS
SYSTEM SETUP
POWER SYSTEM
menu. See the Power
System section of chapter 5 for details.
6.4.5 FlexElements
ACTUAL VALUES
METERING
FLEXELEMENTS
FLEXELEMENT 1(16)
Voltage harmonics are calculated only for Wye connected phase VTs. Ensure that the
SYSTEM SETUP
AC INPUTS
VOLTAGE BANK F5
PHASE VT XX CONNECTION
setting is “Wye” to enable voltage harmonics metering.
SYNCHROCHECK 1
SYNCHROCHECK 1 DELTA
VOLT: 0.000 kV
SYNCHROCHECK 1 DELTA
FREQ: 0.00
Hz
SYNCHROCHECK 1
DELTA PHASE: 0.0°
SYNCHROCHECK 1
SYNSCP D_PH: 0.0°
SYNCHROCHECK 1
V1 MAG: 0.000 kv
SYNCHROCHECK 1
V1 ANG: 0.0°
SYNCHROCHECK 1
V2 MAG: 0.000 kV
SYNCHROCHECK 1
V2 ANG: 0.0°
SYNCHROCHECK 1 PROJ
V2 MAG: 0.000 kV
SYNCHROCHECK 1 PROJ
V2 ANG: 0.0°
SYNCHROCHECK 1 PROJ
DELTA_PHASE: 0.0°
SYNCHROCHECK 1 PROJ
SYNSCP D_PH: 0.0°
TRACKING FREQUENCY
TRACKING FREQUENCY:
60.00 Hz
FLEXELEMENT 1
FLEXELEMENT 1
OpSig:
0.000