5-16
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
3.
Modify the user access rights by enabling or disabling one or more of the check boxes.
The table outlines access rights.
Table 5-2: Access rights summary
4.
Click
OK
to save the changes.
5.3.1.4 CyberSentry security
The EnerVista software provides the means to configure and authenticate the N60 access using either a server or the
device. Access to functions depends on user role.
The login screen of EnerVista has two options for access to the N60, these being Server and Device authentication.
Field
Description
Delete Entry
Deletes the user account when exiting the user management window
Actual Values
Allows the user to read actual values
Settings
Allows the user to read setting values
Commands
Allows the user to execute commands
Event Recorder
Allows the user to use the digital fault recorder
FlexLogic
Allows the user to read FlexLogic values
Update Info
Allows the user to write to any function to which they have read privileges. When any of the
Settings
,
Event
Recorder
, and
FlexLogic
check boxes are enabled by themselves, the user is granted read access. When
any of them are enabled in conjunction with the
Update Info
box, they are granted read and write access.
The user is not granted write access to functions that are not enabled, even if the
Update Info
field is
enabled.
Admin
When this check box is enabled, the user becomes an EnerVista UR Setup administrator and has all
administrative rights. Exercise caution when granting administrator rights.
This feature requires a CyberSentry software option. See the Order Codes section in chapter 2 for details.